  • 400B / LF400B

    400B / LF400B

    mes 400B is a reduced pressure backflow assembly. Production began in 2003. The Ames 400B is the same as the Watts model 919. The body is made of bronze. The checks are a poppet design. Check covers unscrew from body. The check springs are not contained. There is tension from the relief valve spring as you remove the cover. For repair information see Watts 919 info.

    Repair Parts are the same as Watts LF919 click here to view!

    This series is currently Obsolete!

     

  • 4000B / LF4000B

    4000B / LF4000B

    The Ames 4000B is a reduced pressure backflow assembly. In 1997 the Ames Company was bought by the Watts Regulator Company. Ames began to market the Watts 009 series as the Ames 4000B series. For repair information see Watts model 009 info.

    Repair Parts are the same as Watts LF009 click here to view!

     

      

  • 4000SS (Small Diameter)

    4000SS (Small Diameter)

    Ames model 4000SS were available in sizes 3/4"-2". They were made from 1990 and discontinued in 1997. They were stainless steel body with relief valve mounted under the unit.

    This model is currenlty obsolete! Some parts do remain, please call for availability:

    Chicago Office: (866) 836-8692

    Dallas Office: (866) 562-7740

    Detroit Office: (844) 727-8742

    Indianapolis Office: (877) 353-4386

    Denver Office: (844) 622-0186


  • C400 / C400N / C400Z

    C400 / C400N / C400Z

    Ames Series C400, C400N, C400Z Reduced Pressure Zone Assemblies prevent the reverse flow of polluted water from entering into the potable water supply due to backsiphonage and or backpressure. It consists of stainless steel body, sleeve and torsion spring check valves. Series C400, C400N, C400Z has a compact design that is 70% lighter than traditional designs, and is ideal for health hazard piping applications for protection against backsiphonage or backpressure. Check with local water authorities for installation requirements. Maximum Working Pressure: 175psi

    Repair Parts are the same as Watts 957 click here to view!

     

  • M400 / M400N / M400Z

    M400 / M400N / M400Z

    Ames Series M400, M400N, M400Z Reduced Pressure Zone Assemblies prevent the reverse flow of polluted water from entering into the potable water supply due to backsiphonage and or backpressure. It consists of stainless steel body, sleeve and torsion spring check valves. Series M400, M400N, M400Z features the certified lowest pressure loss, a compact design that is 70% lighter than traditional designs and is ideal for health hazard piping applications for protection against backsiphonage or backpressure. Check with local water authorities for installation requirements. Maximum Working Pressure: 175psi

  • 4000SS

    4000SS

    he Ames 4000ss backflow preventer is a reduced pressure assemblies. Discontinued on the 3/4"-2" size in 1997. The body is fabricated stainless steel and has a single top bolted entry access to the checks. The relief valve is mounted under the check body and has an external sensing line. On the 3/4"-2" size assembly there are several versions of the relief valve utilized over the years. The checks are a cam operated design which is made of glass filled Noryl. All versions have a modular check design so the springs will be contained and the seats will be replaceable. From 1990-1992 the 3/4"-2" size utilized an internal ball valve shut off design where the ball valve is built into the body of the assembly. From 1992 an external ball valve was externally screwed onto the body of the assembly. The 2 1/2" and 3" end to end varies by 5/8" due to a manufacturing design change of the end flanges. The check mechanism on the 2 1/2"-12" is made of glass filled Noryl. The check design is a cam operated mechanism. In the 2 1/2"-10" sizes the check modules are not repairable and the whole check module must be replaced for a proper repair. The relief is mounted under the main body and supplied by an external relief valve sensing line.

    Repair Parts are the same as Watts 994 click here to view!

     

  • 4000CIV

    4000CIV

    Series 4000CIV Reduced Pressure Zone Assemblies are designed to provide cross-connection control protection of the potable water supply in accordance with national plumbing codes. This series can be utilized in a variety of installations, including health hazard cross-connections in plumbing systems or for containment at the service line entrance. With its exclusive relief valve design incorporating the "air-in/water-out" principle, it provides substantially improved relief valve discharge performance during the emergency conditions of combined backsiphonage and backpressure with both checks fouled. Maximum Working Pressure: 175psi

    Repair Parts are the same as Watts 909 Click Here to View!

    This series is currently Obsolete!

     

     

  • 4000RP

    4000RP

    The Ames 4000RP is a reduced pressure backflow assemblies. The 4" and 6" were discontinued in 1995. The 8" and 10" were discontinued in 2005. The bodies are welded steel which are fused epoxy coated. The internal check parts are stainless steel. with the check seats constructed of bronze. Special tools are required for proper repair. First check uses a tower mount design which requires the tong tool for proper repair. The second check uses a side mount check mechanism which requires a retainer clip tool for proper repair. The check springs are contained when the covers are removed. Check seats are replaceable and a seat removal tool is required to change them. The check mechanism uses a knuckle joint design. The checks are vulcanized clapper plates instead of rubber discs. The relief valve spring is not contained. The relief valve body is removable from the check body and has an external sensing line.

    This model is currenlty obsolete! Some parts do remain, please call for availability:

    Chicago Office: (866) 836-8692

    Dallas Office: (866) 562-7740

    Detroit Office: (844) 727-8742

    Indianapolis Office: (877) 353-4386

    Denver Office (844) 622-0186


  • 4000BLT

    4000BLT

    Ames Model 4000BLT Portable Hydrant Meter Backflow Preventers prevent the reverse flow of polluted from entering into the potable water supply where flow is in one direction and the possibility of cross-connections exists, such as at a fire hydrant or other non-permanent installation. It consists of stainless steel body construction with stainless steel internal parts. Its portable, lightweight design provides long-term service with minimal maintenance. Series 4000BLT is ideal for use on existing hydrant meter hookups. Factory assembled and tested. Various inlet and outlet sizes available.

    Repair Parts are the same as Watts 994BLT click here to view!

     

  • 6000HMB

    6000HMB

    Ames Model 6000HMB Portable Hydrant Meter Backflow Preventers prevent the reverse flow of polluted water from entering into the potable water supply where flow is in one direction and the possibility of cross-connections exists, such as at a fire hydrant or other non-permanent installation. It consists of a stainless steel body construction with stainless steel internal parts, meter housing, measuring element, and permanently sealed register to measure flow and protect the meter and backflow preventer from damage due to excessive flow. Series 6000HMB meets AWWA C701 meter requirements and is ideal for use in existing hydrant meter hookups. Factory assembled and tested.

    Repair Parts are the same as Watts 994HBM click here to view!

     

  • 4000B-FP

    4000B-FP

    Ames Series 4000B-FP Reduced Pressure Zone Assemblies with Gear Operated Slow Close Isolation Valves prevent the reverse flow of polluted water from entering into the potable water supply due to backsiphonage and or backpressure. It consists of bronze body construction, two, in-line independent check valves, replaceable check seats with an intermediate relief valve, and ball valve test cocks. Series 4000B-FP is ideal for protection of health hazard cross-connections or for containment at the service line entrance. Check with local water authorities for installation requirements. Maximum Working Pressure: 175psi