• Home
  • News - How To - Repair Wilkins 375

Always follow manufacturer’s repair instructions.

This is an expanded guide that is following the
manufacturer’s exact repair instructions. Test Gauge Inc. has
provided tips to make repair safer and easier based on
industry experts.

Repairing a backflow preventer so it meets the original
specifications is a critical step in protecting our potable
water resources.

Removing the Vessel

Start by closing both your inlet and outlet ball valves. Next, Open No.2, No. 3 and No. 4 test cocks to release pressure from valve.

Unscrew clamp screws, and remove clamp that is holding the vessel in place.

Once the clamp is loose, pull it straight up and out of the body.

If the clamp will not come loose, or you’re worried about breaking it, you can thread 1 of the screws that were removed earlier into the threaded center hole to help loosen it. (1” size only)

Now that the clamp is removed, you may slide sleeve

(black plastic piece with 2 screw holes) toward inlet pipe. Slide valve body toward inlet and lift upward.

The valve body is now free, the #1 and #2 check

assemblies can be cleaned and repaired as needed.

Before proceeding onto further repairs, remove the inlet and outlet o-rings pictured below. Tip: slide them on #1 ball valve handle so they do not get misplaced while repairing the check assemblies.

Using finger or blunt object, push in outlet end of body, both checks should slide out the body inlet

If you are unable to remove the checks by pushing with fingers, a nut driver will work on the ½”, ¾” & 1” sizes. On the 1” size only, using one of the ball valve handles is also a quick and easy option.

Pictured above are the complete #1 and #2 check assemblies once they are removed from the valve body.

Twist spring retainers counter-clockwise to remove from seat and access poppets

Inspect the rubber seal ring for cuts or embedded debris.

To remove seal ring, remove screw and seal ring retainer. If the reverse side of the seal ring is unused, it is possible to invert the seal ring. This would be considered a temporary solution to fixing a fouled check and should be replaced with a new seal ring as soon as possible.

Inspect seat surface for nicks or dings and replace if necessary. Use fingernail to check for dings. Re-grease seat o-rings

Care should be taken to make sure the heavy spring is installed in the No. 1 check valve

When properly pushed all of the way in, the #1 check assembly will sit flush with the front of the valve body.

Drop #2 check assembly in body. Then drop #1 check assembly in and turn until #1 spring retainer lines up with #2 seat. Then push both assemblies into body.

Before re-installing sleeve on the #1 ball valve, check to make sure the sleeve o-ring is not damaged and grease accordingly.

Also, make sure that sleeve has been cleaned and that there is no debris on any sealing surface before installation.

After sleeve is installed, set valve body back in place and tighten screws down on clamp.

Do not over tighten clamp screws as this can cause leak at the sleeve o-ring.

Remove relief valve cover screws.

Once all screws are loosened, pull off cover.

The relief valve spring is not contained on this RPZ. After removing cover, set the spring to the side until you are ready to re-install.

Inspect relief valve seat for wear on seating surface. If damaged, replace seat and seat o-ring.

The “cover” that was removed from the relief valve contains the diaphragm and stem assembly. To remove these components, gently pull on diaphragm to remove the cartridge assembly

Disassemble cartridge by unscrewing relief valve retaining screw. This will also allow inspection of the relief valve seal ring & diaphragm.

Pay close attention to the diaphragm if it is removed. It only goes on 1 way. Replace required parts and apply a light coat of grease to plunger o-ring, and place on plunger.